A portable monitor protects the person wearing it. A pump seal that starts leaking at 2 a.m., in a part of the unit nobody is walking through, gets caught only by the instruments bolted to the structure. That is the job of a fixed gas detection system: watch the process area continuously, raise an alarm where operators will see it, and trigger the response before a release turns into an exposure or an ignition. In a petrochemical unit, the specification also has to meet two requirements: a hazardous-area rating that matches the classification of the area, and sensors that can tell the target gas apart from everything else in the process matrix.
This guide walks through how to specify a system, from the gas list to the controller.
What a fixed gas detection system includes
A fixed gas detection system has three layers:
- Detectors or transmitters mounted in the process area. Each one carries a sensor for a specific gas or gas family and converts the reading into a signal, typically 4 to 20 mA, Modbus RS-485 or relay contacts.
- A controller in a safe area that receives those signals, shows readings, and manages alarm levels. Controllers are sized by channel count. Inteccon’s catalog includes the GFG GMA 200-MW4 (up to 4 channels), the GFG GMA 200-MW16 (up to 16 channels) and the Sensidyne 7200 controller (16 to 64 channels).
- Outputs and actions: horns and beacons, a link to the plant’s control or safety system, and in some designs automatic actions such as ventilation or shutdown.
The order of the specification matters: decide what to detect, then where the detectors can legally and physically go, then how the signals are handled.
Step 1: build the gas list from the process
Each gas in a petrochemical unit calls for a different sensor technology and a different alarm reference. The table summarizes the most common cases and the references to check before setting alarm points.
Hazard | Reference values to check | Typical sensor technology | Inteccon option |
|---|---|---|---|
Combustible gases and vapors | Percentage of the lower explosive limit (%LEL) | Catalytic or infrared | |
Hydrogen sulfide (H2S) | OSHA PEL: 20 ppm ceiling, 50 ppm 10-minute peak. NIOSH IDLH: 100 ppm | Electrochemical | SensAir toxic versions |
Volatile organic compounds | Compound-specific exposure limits | Photoionization (PID) | |
Benzene | OSHA PEL: 1 ppm TWA, 5 ppm STEL, 0.5 ppm action level. NIOSH REL: 0.1 ppm TWA | Benzene-specific PID |
A few points behind the table:
- Combustibles. Flammable gas detection is reported as %LEL, so the alarm points describe how close the atmosphere is to being ignitable.
- H2S is both toxic and flammable. NIOSH lists its LEL at 4.0%, which means the toxic thresholds are reached long before the flammable one. Toxic detection drives the design.
- VOCs. A PID responds to many compounds at once. Falco, according to Ion Science, uses a 10.6 eV lamp and is offered in 0 to 10, 0 to 50, 0 to 1,000 and 0 to 3,000 ppm ranges, in pumped and diffusion models.
- Benzene is the hard case. A standard PID reads benzene together with toluene, xylene and other aromatics, so a high reading does not tell you which compound is present. Ion Science describes Titan as a fixed, benzene-specific monitor: its sampling method separates benzene from interfering gases such as toluene, xylene and methane, with a 0 to 20 ppm range and one measurement per minute.
Step 2: match the hazardous-area rating to the classification
Every device mounted in a classified area needs a certification that matches that area. In the U.S. this is expressed under the NEC as Class I, Division 1 or 2, or as Zones; outside North America the ATEX and IECEx Zone system applies. Confirm the exact marking on the datasheet and on the device; a general “hazardous-area approved” claim does not tell you whether it matches the area.
Two protection concepts appear constantly in fixed detection:
- Explosion-proof or flameproof (XP, Ex d). The enclosure contains any internal ignition and prevents it from reaching the outside atmosphere.
- Intrinsic safety (Ex i). The circuit is designed so it cannot release enough energy to ignite the atmosphere.
Some detectors combine both. Ion Science’s Falco datasheet lists ATEX II 2G Ex db ib IIC T4 Gb and UL/CSA Class 1, Division 1, Groups A, B, C, D, T4. Sensidyne describes SensAir as housed in an explosion-proof enclosure, certified for Class 1, Division 1 and Division 2, and ATEX/IECEx Zone 1 and Zone 2. Ion Science states that Titan is certified to ATEX, IECEx, UL and CSA standards.
The practical rule: confirm the gas group and temperature class on the marking against the area classification drawing, for every detector and every accessory mounted in the area.
Step 3: place detectors where the gas will actually be
A fixed detector only sees the gas that reaches it. Placement depends on where releases can occur (pump seals, flanges, valves, sample points, loading racks), on the density and temperature of the released gas, and on wind and ventilation patterns in the unit.
Two references help structure the decision:
- IEC 60079-29-2 gives guidance and recommended practice for the selection, installation, safe use and maintenance of detectors for flammable gases and oxygen.
- ISA-TR84.00.07-2018, Guidance on the Evaluation of Fire, Combustible Gas, and Toxic Gas System Effectiveness, addresses fire and gas systems in process industry applications. It uses detector coverage and safety availability as performance metrics, and it is one of the references used in fire and gas mapping studies to decide detector locations.
For toxic gases, also consider where people breathe. A detector placed for early leak detection at a seal may not represent the exposure of an operator working a few meters away, so fixed systems and personal monitoring work together.
Step 4: plan the controller, alarms and maintenance
Once the detector count is known, size the controller with spare channels for future additions, define alarm levels per gas, and decide which alarms stay local and which go to the control room or safety system. Check that each transmitter’s output (4 to 20 mA, Modbus or relays) is supported by the controller.
Maintenance belongs in the specification. Sensor life, calibration frequency and the effort needed to service a detector in a classified area all add up over the life of the system. Ask for the expected sensor life per gas (Sensidyne, for example, lists 3 years for SensAir combustible and H2S sensors and 2 years for oxygen), the calibration procedure, and whether it can be done with the detector in place. IEC 60079-29-2 covers the maintenance side for flammable gas and oxygen detectors.
Frequently asked questions
What is a fixed gas detection system?
It is a network of permanently installed gas detectors connected to a controller that displays readings and triggers alarms or actions when a gas exceeds a set point. It monitors an area continuously, whether or not anyone is present.
What is the difference between fixed and portable gas detectors?
A portable detector protects the person carrying it and moves with them. A fixed detector protects an area and the equipment in it around the clock. Petrochemical sites use both.
Where should fixed gas detectors be installed?
Near likely release points and along the paths the gas will follow, considering its density, temperature and air movement. IEC 60079-29-2 and gas mapping under ISA-TR84.00.07 are the usual references for placement.
Can a standard PID detect benzene in a refinery?
A standard PID responds to benzene but also to toluene, xylene and other compounds, so it cannot confirm that the reading is benzene. A benzene-specific instrument such as Ion Science’s Titan is designed to separate benzene from those interferents.
What does Class I, Division 1 mean?
It is the NEC designation for locations where flammable gases or vapors can be present under normal operating conditions. Equipment installed there must carry a matching certification.
Conclusion
A fixed gas detection system that works in a petrochemical unit starts with an honest gas list, uses sensors that can identify the target gas, carries certifications that match the area classification, and puts detectors where the gas will go. Inteccon’s catalog includes fixed detection lines from Ion Science, Sensidyne, GFG and Prosense, and Inteccon can help match each point of the specification to equipment. See the full range in the fixed gas detection systems category.