Compressed air monitoring system is designed to ensure the quality and breathability of compressed air. It features an electrochemical Carbon Monoxide (CO) sensor with a range of 0-99 ppm and an electrochemical oxygen sensor with a range of 0-25% Vol. The system also measures dew point from -112°F to 68°F. It has an optional three-stage filtration panel that effectively removes particulate matter, oil vapors, and hydrocarbons from the air line. The system has a clear LCD display and an audible and visual alarm that alerts the user when CO levels exceed 5 and 10 ppm, oxygen levels fall below 19.5% and 23.5% Vol, and when the dew point reaches 4°F. The housing is made of high-strength NEMA 4X material and has a high-pressure connection of 30 to 145 psi. The system operates on 110 VAC or 12-24 VDC and has a 2-hour charge cycle for up to 24 hours of operation.

  • Electrochemical sensor for measuring Carbon Monoxide (CO) in the range of 0-99 ppm.
  • Electrochemical sensor for measuring Oxygen (O2) in a range of 0-25% Vol.
  • Dew point from -112°F to 68°F
  • Optional efficient three-stage filtration panel for removal of particulate matter, oil vapors and hydrocarbons from the airline.
  • LCD display
  • Audible and visual alarm set at 5 and 10 ppm CO, 19.5% and 23.5% Vol. Oxygen, 4 °F Dew Point
  • High resistance NEMA 4X housing.
  • High pressure connection 30 to 145 psi
  • NO/NC relays depending on the model
  • Operation via 110 VAC or 12 – 24 VDC for up to 24 hours with a 2-hour charge cycle